Bundle conductors
Bundle conductors are used to reduce corona losses and audible noise. Bundle conductors consist of several conductor cables connected by non-conducting spacers. For 220 kV lines, two-conductor bundles are usually used, for 380 kV lines usually three or even four. American Electric Power[4] is building 765 kV lines using six conductors per phase in a bundle. Spacers must resist the forces due to wind, and magnetic forces during a short-circuit.
Bundle conductors are used to increase the amount of current that may be carried in a line. Due to the skin effect, ampacity of conductors is not proportional to cross section, for the larger sizes. Therefore, bundle conductors may carry more current for a given weight.
A bundle conductor results in lower reactance, compared to a single conductor. It reduces corona discharge loss at extra high voltage (EHV) and interference with communication systems. It also reduces voltage gradient in that range of voltage.
As a disadvantage, the bundle conductors have higher wind loading.